LOGO

Our Services

HOT INSULATION

Hot insulation shall generally be applied to equipment and piping operating at 60℃ and above, except for the case where heat loss is desired. Where heat loss is to be restricted, however, full heat conservation insulation (HO) shall be applied, even when the operating temperature is below 60℃ with various insulation materials.

DUAL TEMPRATURE INSULATION

Dual Temperature insulation shall be provided for piping and equipment which operate normally at cold temperature below 0℃. but which are subject to high temperature above 60℃ during regeneration.

PERSONAL PROTECTION INSULATION

Personnel protection insulation (P) shall be applied to non insulated equipment and piping operating at 60℃ and above, where operators, while working, can inadvertently come in contact with them.

JACKETING / CLADDING

The sheet metal cladding for jacketing to provide protection towards whether, mechanical wear and tear etc.. by using various flat, stucco embossed & corrugated metals.

COLD INSULATION

Cold insulation (C) shall be applied to equipment and piping operating at temperature below 0℃. where reduction of heat gain and prevention of surface condensation is desired.All Protrusions in cold insulation shall be insulated by four (4) times the of thickness of insulation.

  • 1) Skirt or leg of tower and tank
  • 2) Pipe supports
  • 3) Branch of vent and drain piping

ANTI – SWEAT INSULATION

Anti-Sweat insulation (A) shall be applied to equipment and piping operating at above 0℃ but below the ambient temperature, if surface condensation of moisture would provide an adverse effect as below:-

  • 1) Electrical hazard
  • 2) Damage to equipment
  • 3) Surface condensation providing discomfort to working

ACOUSTIC INSULATION

It’s the open, porous structure of stone wool that makes it highly efficient in protecting against noise pollution. In ceilings, noise screens, around noisy machines, in walls, roofs and floors and even underneath rail tracks, Rockwool insulation acts as a natural and effective sound barrier. For building acoustics we have acoustic door, studio, home theatre, and auditorium and wall, While in industrial acoustics we have exhaust silencer insulation, acoustic canopy, acoustic enclosure, duct silencer insulation, acoustic louvers, acoustic barrier, spark arrester insulation, vent silencer and circular silencer insulation.Our services ranges from products supply, designing, fabricating and installation of an assigned acoustic projects.

CODES & STANDARDS

We follow and meet requirements prescribed in BS & ASTM Standard for thermal insulation

(1) American Society for Testing and Materials (ASTM)

  • ASTM C168 : Standard Terminology Related to Thermal Insulating Materials
  • ASTM C 533 : Standard Specification for Calcium silicate Block Insulation for Piping.
  • ASTM C547 : Standard Specification for Mineral Fiber Pipe Insulation
  • ASTM C552 : Standard Specification for Cellular Glass Thermal Insulation
  • ASTM C553 : Standard Specification for Mineral Fiber Blanket Thermal Insulation for Commercial and Industrial Applications
  • ASTM C591 : Standard Specification for unfaced Preformed Rigid Cellular Polyisocyanurate Thermal Insulation
  • ASTM C592 : Standard Specification for Mineral Fiber Blanket Insulation and Blanket-type Insulation
  • ASTM C612 : Standard Specification for Mineral Fiber Block and Board Thermal Insulation
  • ASTM C795 : Standard Specification for Thermal Insulation for Use in Contact with Austenitic Stainless Steel
  • ASTM A167 : Standard Specification for Stainless and Heat-Resisting Chromium-Nickel Steel Plate, Sheet, and Strip
  • ASTM A240 : Standard Specification for Heat-Resisting Chromium and Chromium- nickel Stainless Steel Plate, Sheet, and Strip for Pressure Vessels
  • ASTM A653 : Standard Specification for Steel Sheet, Zinc-Coated(Galvanized) or Zinc-Iron Alloy-Coated (Galvanized) by the Hot-Dip Process
  • ASTM E96 : Standard Test Methods for Water Vapor Transmission of Materials

Asian Thermal Insulation (India) Pvt. Ltd.@2015 | All Rights Reserved